Power Factor Correction & Harmonic Mitigation
Advanced Static Var Generator (ASVG) Solution
Client
ASIC NSW
Location
Sydney, NSW
Project Type
Power Quality Upgrade
Delivered By
Micron Group
Power factor correction from 0.6–0.9 to 0.99 (Unity), achieving a 65% efficiency gain
Before
0.6 - 0.9
After
0.99
Improvement
+65%
Total Harmonic Distortion (THDI%) reduced from up to 500% on Neutral to less than 8% across all phases
Status
Critical - Non-Compliant
All phases exceed AS/NZS limits
Status
Excellent - Fully Compliant
All phases below AS/NZS limits
Peak Before
500% (Neutral)
Avg Before
92% (Phases)
After
< 8% (All)
Compliance
AS/NZS 61000
Phase current balancing and neutral current reduction achieving optimal electrical distribution
Status
Unbalanced - High Neutral Current
Status
Perfectly Balanced
Neutral Before
107 A
Neutral After
40 A
Reduction
-63%
Balance
Optimized
Three-phase approach to power quality optimization
Comprehensive electrical system transformation
Parameter
Power Factor
Before
0.6 – 0.9
After
0.99 (Unity)
+65% Efficiency Gain
Optimized
Parameter
Harmonics (THDI%)
Before
Up to 500% Neutral
After
< 8% All Phases
> 490% Reduction
Compliant
Parameter
Load Balance (A)
Before
L1: 338 / L2: 369 / L3: 364 / N: 107
After
L1: 335 / L2: 322 / L3: 336 / N: 40
Perfect Balance
Achieved
Parameter
Voltage Stability
Before
257.2 V Spikes
After
< 240 V Steady
Stabilised
Controlled
Unity Power Factor
THDI All Phases
Neutral Current
AS/NZS Compliant